150kw 188kVA Prime Standby Emergency Germany Deutz Generator

Product Details
Customization: Available
Type: Self-Starting Diesel Generator
Installation Method: Fixed
Still deciding? Get samples of US$ 13500/Piece
Request Sample
Manufacturer/Factory, Trading Company

360° Virtual Tour

Diamond Member Since 2018

Suppliers with verified business licenses

Audited Supplier

Audited by an independent third-party inspection agency

Registered Capital
65000000 RMB
Plant Area
1001~2000 square meters
  • 150kw 188kVA Prime Standby Emergency Germany Deutz Generator
  • 150kw 188kVA Prime Standby Emergency Germany Deutz Generator
  • 150kw 188kVA Prime Standby Emergency Germany Deutz Generator
  • 150kw 188kVA Prime Standby Emergency Germany Deutz Generator
  • 150kw 188kVA Prime Standby Emergency Germany Deutz Generator
  • 150kw 188kVA Prime Standby Emergency Germany Deutz Generator
Find Similar Products

Basic Info.

Model NO.
BS-D188
Stroke
Four Stroke
Cooling Method
Water Cooling
Output Type
AC Three Phase
Speed
Speed
Conditions of Use
Land Use
Usage
Common Units, Standby Unit, Emergency Crew
Landuse Type of Unit
Low Noise
Excitation Mode
AC Rotating Exciter
Engine
Deutz Bf6m1013fcg2
Alternator
Stanford
Controller
Smartgen, Deepsea...
Starting Method
Electric Start
Power
150kw/188kVA
ATS
Optional
Color
as Per Request
Frequency
50Hz
Voltage
400V
Transport Package
Packed in Plywood Cases or Wooden Cases or Foam, E
Specification
As for power
Trademark
BOSSPOWER
Origin
China
HS Code
85021200
Production Capacity
100 Sets / Month

Product Description

PRODUCT DESCRIPTION  
Frequency: 50HZ;Rotating speed: 1500Rpm
Model Power(KW) Capacity(KVA) Rated current(A) Engine Model Original Stanford
BS-D60 48  60 86.6 BF4M2012 UCI224E
BS-D75 60 75 1082 BF4M2012C UCI224F
BS-D100 80 100 144.3 BF4M1013EC UCI274C
BS-D125 100 125 180.4 BF4M1013FC UCI274D
BS-D160 128 160 230.9 BF6M1013EC UCI274F
BS-D188 150 155 270.6 BF6M1013FCG2 UCI274G
BS-D200 160 200 288.6 BF6M1013FCG3 UCI274H
BS-D230 184 230 331.9 BF6M1015-LA GA UCD274J
BS-D250 200 250 360.8 BF6M1015C-LA G1A UCD274K
BS-D300 240 300 433 BF6M1015C-LA G2A HCI444D
BS-D325 260 325 469 BF6M1015C-LA G3A HCI444ES
BS-D350 280 350 505 BF6M1015C-LA G4 HCI444E
BS-D375 300 375 541.2 BF6M1015CP-LA G HCI444FS
BS-D438 350 438 631.4 BF8M1015C-LA G1A HCI544C
BS-D450 360 450 649.5 BF8M1015C-LA G2 HCI544C
BS-D463 370 463 667.5 BF8M1015CP-LA G1A HCI544C
BS-D500 400 500 721.7 BF8M1015CP-LA G2 HCI544C
BS-D550 440 550 793.8 BF8M1015CP-LA G4 HCI544D
BS-D575 460 575 829.9 BF8M1015CP-LA G5 HCI544E
           
Frequency: 60HZ;Rotating speed: 1800Rpm
Model Power(KW) Capacity(KVA) Rated current(A) Engine Model Stanford Type
BS-D70 56 70 101 BF4M2012 UCI224E
BS-D88 70 87.5 126.3 BF4M2012C UCI224F
BS-D114 91 114 164 BF4M1013EC UCI274C
BS-D130 104 130 187.6 BF4M1013FC UCI274D
BS-D168 134 168 241.7 BF6M1013EC UCI274E
BS-D190 152 190 274.2 BF6M1013FCG2 UCI274F
BS-D213 170 213 306.7 BF6M1013FCG3 UCI274G
BS-D250 200 250 360.8 BF6M1015-LA GA UCI274J
BS-D275 220 275 396.9 BF6M1015C-LA G1A UCI274J
BS-D313 250 313 451 BF6M1015C-LA G2A HCI444D
BS-D350 280 350 505 BF6M1015C-LA G3A HCI444D
BS-D456 365 456 658.5 BF6M1015C-LA G4 HCI444F
BS-D488 390 488 703.6 BF6M1015CP-LA G HCI544C
More specific parameters to choose.
Genset Model BS-D188
Prime Power (kw/kva) 150 / 188 Standby Power(kw/kva) 165 / 206
Voltage (v) 400 Rated Speed (rpm) 1500
Frequency (Hz) 50 Rated Current (A) 202
Connection: 3 phase Power Factor: 0.8
Engine Model: BF6M1013FCG2 Alternator Model: UCI274G
Net Weight (kgs)-Silent 2200 Dimensions (mm)-Silent 3250x1200x1800
Engine Parameter:
Manufacturer/Model:
Engine type:
Fuel System:
Displacement:
Bore x Stroke
Compression Ratio:
Max. Power:
Governing System:
DEUTZ BF6M1013FCG2 
4-Cycle,6-Cylinder in line, Turbo charged

single injection pumps
7.15 L
108 x 130 mm
19 : 1
183 KW
Electrical. gov
Exhaust System
Exhaust temperature:
Max. Allowed Back Pressure:
Exhaust Gas flow:
540ºC
30 mbar
2108m3/h
Intake System
Max. intake depression (Switch setting)
Combustion air volume
25 mbar
743.9 m3/h
Fuel System
25% Load (Prime):
50% Load (Prime):
75% Load (Prime):
100% Load (Prime):
11.1 liters / hr
20.3 liters / hr
30.2 liters / hr
40.6 liters / hr
Lube System
Oil Capacity:
Oil Consumption (as % of fuel consumption):
Min.Oil Pressure (warning):
Min.Oil Pressure (shut down):
Max.permissible oil temperature(oil pan)
31 liters
0.3
2.7 bar
2 bar
130 ºC
Cooling system
Max.perm.coolant outlet temperature:
Max.temperature of coolant (warning):
Max. temperature of coolant (shutdown):
Temperature at which thermostat starts to open:
Temperature at which thermostat is fully open
Temperature at CAC outlet at standard conditions
Coolant capacity (engine):
Coolant capacity (incl. cooling unit):
Air to boil (max. permissible cool. air temp. at fan):
Fan power consumption:
Cooling air flow:
Air pressure loss, external:

105ºC
108ºC
110ºC
83ºC

98ºC

40ºC

9.8 L
27.3 L
55ºC

7.2KW
11520 m3/h
1.5 mbar
 
Alternator Parameter:        Basic Information
The alternators meet the standards of:
GB755, BS5000, VDE00530, NEMAMG1-22,IED34-1,CSA22.2 and AS1350
Technical Data:
Manufacturer:
Phases:
Bearing numbers:
Power Factor:
Protection Class:
Altitude Condition:
Excitation:
Insulation class/Temp. rise class:
Tel. Influence Factor TIF:
Tel. Harmonic Factor THF:
Steady State Voltage Regulation:
Alternator Capacity:
Efficiency:
 STANFORD UCI274G
 3
  1
 0.8
IP23
 ≤1000M
 Brushless, self-excitation
  H / H
  <50
 <2%
 ≤±1%
150KW
 92.5%
 
 
PRODUCT SHOWS  

150kw 188kVA Prime Standby Emergency Germany Deutz Generator


 
PRODUCT ADVANTAGE  
 
(1)The silent canopy we use cold-rolled sheet, all positions are stronger.
 
(2)Our spraying plastics all go through pre-treatment of pickling and phosphating, so that the surface of the
    
    painting will not change color even if placed outside for five years.

 
(3)Canopy color painted by customer's requirement.
 
(4)Strict test including 50% load,75% load,100% load and 110% Load .
 
(5)Forklift mouth in base frame for easy loading and discharging.
 
(6)Logo made by customer's requirement if order quantity ≥10units or a full container.

150kw 188kVA Prime Standby Emergency Germany Deutz Generator
150kw 188kVA Prime Standby Emergency Germany Deutz Generator150kw 188kVA Prime Standby Emergency Germany Deutz Generator
FAQ  
Q: Do you offer OEM service?
A: Yes
Q: What is your payment term?
A: 30% T/T in advance, the rest payment before shipment.  Or irrevocable L/C.
Q: What is your lead time?
A: About 30 days after receiving deposit or original L/C.But if your order with some special design, then the
    delivery time is longer.

Q: What certificates do you have?
A: We have CE, ISO. And we can apply for specific certificate for different country such as SONCAP for Nigeria,
     CIQ for Egypt, SASO for Saudi Arabia, etc

Q:What is your MOQ?
A: Above 1pc
Q. Which port do you often use when export?
A: Fuzhou Port, or as customer request.
Q.How to choose the power?
A.:Collect all power of your equipments,take the current into your consideration.
Q.What is the difference between Prime power and Standby power?
A.:Prime power is 12hours continous power,one hour 10% over load in every 12 running hours is allowed.
Standby power is the limit value of maximum output for emergency use. Overloading is prohibited
Q.What about the warranty
Guarantee for one year or 1000 hours (accord to whichever reach first) from ex-factory date.During the guarantee period,
our company will provide the free easy damaged spare part for problems caused by our quality of production or raw material
except the damageable spare parts of diesel engine caused by customer's incorrect man made operation.After expiration,
our company provides cost parts maintenance for gen-set.

 
CONTACT US   

 

Send your message to this supplier

*From:
*To:
*Message:

Enter between 20 to 4,000 characters.

This is not what you are looking for? Post a Sourcing Request Now